Gas Phase Filtration
Introduction
As an alternative to gas phase filtration equipment that can be integrated within Bebco Wall-Mount, Pad, and Packaged Units, Bebco’s Filtration Units in these independent, stand-alone configurations provide corrosive and toxic environment filtration solutions for Class I, Division 1 or 2 Hazardous and Unclassified Locations.
All these units feature listed components in fully independent wall, roof, pad, or floor-mount configurations and are available with ETL limited product certification. Options include deep media beds, activated carbon honeycomb cartridges or media filled cell cartridges, along with washable, impregnated or pleated pre and post filters. These units scrub H2S, SO2, NOX, VOC, Chlorine or Ammonia to create a clean environment.
These units include disconnects, monitors, and alarm contacts to control power and detect media saturation or insufficient airflow. Control options include variable speed drives to achieve specific ventilation, recirculation or exchange airflow rates. Additional options include NFPA 496 pressurization, alarm set point and delay features and local or remote emergency shutdown and override controls.