Stainless Steel Wall & Remote Mount NFPA 496 Building Pressurization Units

Specifications

Bebco Model WDP & RDP Units are provided in several sizes and configurations to serve a broad range of domestic industrial and corrosive environment applications. This section provides applicable specifications for the complete range of products we currently offer.

Scroll down or contact a Bebco Sales Associate to learn more…

Click any item to open and click any image to enlarge…

The following chart provides all unit dimensions and weights based on the unit size. Please use this guide
to ensure our product’s compatibility with your specific application!

Model WDP Units

Model Number

Overall Height x Width x Depth

Shipping Weight

WDP-12

37.25" x 16.13" x 28"

340 lbs.

WDP-16

41.25" x 20.18" x 32"

410 lbs.

WDP-20

48.25" x 24.18" x 35"

480 lbs.

WDP-24

56.25" x 28.18" x 39"

555 lbs.

Model WDP Whisper Drive™ Units mount through a framed cutout in the exterior wall of the room or building to be pressurized, which should be oversized by at least 0.25 inches on all sides to permit easy insertion of the Unit and provide clearance for the Interior Trim Bezel’s mounting flange on all sides of the Unit. Please also ensure the structural integrity of the wall selected is sufficient to support the unit’s weight properly, or consider the use of bracing if required.

Model WDP Whisper Drive™ Unit Installation
Details & Considerations

Model RDP Units

Model Number

Overall Height x Width x Depth

Shipping Weight

RDP-12

16.25" x 16.25" x 44.88"

360 lbs.

RDP-16

20.25" x 20.25" x 46.88"

402 lbs.

RDP-20

24.25" x 24.25" x 46.88"

425 lbs.

RDP-24

28.25" x 24.25" x 50.88"

480 lbs.

Model RDP Whisper Drive™ Units may be mounted on an exterior wall or roof and are provided with vibration isolators for field placement to facilitate mounting. Unit may be mounted in any position, but please ensure the structural integrity of the wall or roof location selected is sufficient to support the unit’s weight properly, or consider the use of bracing, if required.

Model RDP Whisper Drive™ Unit Installation
Details & Considerations

RDP Remote Control Station

Model Number

Overall Height x Width x Depth

Shipping Weight

RDP-RCE

18" x 14" x 9.5"

*48 lbs.

The Model RDP Remote Control Station may be mounted on any interior or exterior wall using cast bolt tabs located on the top and bottom sides of the Control Station Enclosure. Please ensure the structural integrity of the wall selected is sufficient to support the station’s weight properly, or consider the use of bracing, if required.

Model RDP Whisper Drive™ Unit Remote Control Station
Installation Details & Considerations/p>

This chart provides an overview of minimum and maximum operating temperatures to ensure our unit is compatible with
your specific application.
Please contact a Bebco Sales Associate for applications exceeding the ranges stated below.

Model Number

Minimum to Maximum

Operating Temperature

All Models

-40° F - 120° F

The following chart lists the average and maximum power consumption of Model WDP & RDP Units.
Please contact a Bebco Sales Associate for more information or assistance, if needed.

Model WDP Units

Model Number

Unit Supply Power

Min / Max Current Load

WDP-12

208 / 240 VAC 1Ø, 50 / 60 Hert 20 A

xx / xx

WDP-16

208 / 240 VAC 1Ø, 50 / 60 Hert 20 A

xx / xx

WDP-20

208 / 240 VAC 1Ø, 50 / 60 Hert 20 A

xx / xx

WDP-24

208 / 240 VAC 1Ø, 20 A

xx / xx

All Units require 208 to 240 VAC Single Phase
50 or 60 Hertz Power.

Please contact a Bebco Sales Associate if you require,br> an optional power source.

Model RDP Units

Model Number

Unit Supply Power

Min / Max Current Load

RDP-12

208 / 240 VAC 1Ø, 50 / 60 Hert 20 A

xx / xx

RDP-16

208 / 240 VAC 1Ø, 50 / 60 Hert 20 A

xx / xx

RDP-20

208 / 240 VAC 1Ø, 50 / 60 Hert 20 A

xx / xx

RDP-24

208 / 240 VAC 1Ø, 50 / 60 Hert 20 A

xx / xx

Average Current Load based upon running conditions with primary
fan engaged and all doors sealed

Reliable, industrial-grade materials and components guarantee optimal unit performance in the harshest industrial environments!
Please contact a Bebco Sales Associate for more information, if required.

IC Case Style Housings:

*Painted 14 Gauge Galvanneal Steel

IS Case Style Housings:

*Painted 14 Gauge 304 Stainless Stee

IX Case Style Housings:

*Painted 14 Gauge 316 Stainless Steel

Fan Venturis:

Matches Housing Material

Discharge Grilles & Filters:

Anodized Aluminum

Fan Blades:

Non-sparking Aluminum

Room Pressure Indicator Bodies:

Cast Aluminum w/ Enamel Finish

Room Pressure Indicator Lenses:

Molded Lexan® w/ Neoprene Gasket

Tube & Flame Arrestor Fittings:

316 Stainless Steel & Nylon

Pressure Reference Tubing:

1/4” Heavy Wall Tygon®

Unit Nameplates:

Silkscreened Lexan®

Fastener Hardware:

SS Screws & Bolts

Rear Door Fasteners:

Cast Zinc Body w/ Zinc Bolt & Pawl

Rear Door & Intake Port Gaskets:

Molded & Open Cell Neoprene

Control Wiring:

THHN 18 & 12 Gauge Stranded Wire

Motor Cable & Fittings:

Brass MI Cable & Fittings w/ PVC Jacket

Control Enclosures, Disconnects, Junction Boxes & Fittings:

Cast Aluminum Bodies, Zinc Bolts,

Phenolic Operators & Cast Zinc Bodies

*Paint Finish Specifications:
2 mil epoxy or wash primer base coat and 3-6 mil white textured
Sherwin Williams Polane® urethane finish coat

Lexan® is a registered trademark of the General Electric Corporation.
Tygon® is a registered trademark of the Saint-Gobain Corporation.
All specifications subject to change without notice.

WDP Units

Urethane Coated Galvanneal, 304 Grade or 316 Grade Stainless Steel Housing with Cast Aluminum Control Enclosure & Junction Boxes Neoprene Gaskets & Stainless-Steel Fasteners.

To meet the most demanding corrosion resistance needs, while providing a cost-effective solution, Model WDP Units are offered in 14 gauge seal-welded galvanneal, 304 grade stainless steel or 316 grade stainless steel. These self-contained configurations also contain all other components, as listed on the Material Specifications Table, including as the most notable items the control enclosure, room pressure gauge, motors and junction boxes, along with all related hardware tubing, motor cables, wiring and gaskets.

RDP Units

Urethane Coated Galvanneal, 304 Grade or 316 Grade Stainless Steel Housing with
Neoprene Gaskets & Stainless Steel Fasteners.

Model RDP Unit Housings are offered with materials identical to the WDP Housings, but as configured only feature disconnect switches, as opposed to the broader range of components in Model WDP Units. In some respects, this difference makes Model RDP Units more durable, which is appropriate since they are often located in much more remote locations than their Model WDP counterparts.

Model RDP Remote Control Stations

Cast Aluminum Control Enclosure & Aluminum Gauge with Enamel Finish in 316 Grade Stainless Steel Mounting Plate

Model RDP Remote Control Stations are offered with a cast aluminum NEMA 4 and 7 rated control enclosure, a cast aluminum room pressure indicator with an enamel finish and Lexan® lens, and a 316 grade stainless steel mounting plate, flame arrestors, tubing and fittings to mount and connect the indicator’s differential pressure ports. This Control Station is suitable and intended for indoor or outdoor use, and the room pressure indicator must be tubed to reference external atmospheric pressure or room pressure depending on the Station’s location.

The following chart lists measured data that constitutes a maximum level or average measurement of performance.
Please contact a Bebco Sales Associate for the most accurate information available at time of inquiry or order.

Model WDP Units

Model

Number

Average CFM /

Maximum CFM

Normal / Maximum

Sound Levels

Primary Motor

Maximum RPM

Secondary Motor

Maximum RPM

WDP-12

65.24 / 1370

60 db / 70 db

3000

1725

WDP-16

79.03 / 2450

60 db / 70 db

2000

1725

WDP-20

73.98 / 4069

60 db / 70 db

1725

1725

WDP-24

61.77 / 4633

60 db / 70 db

1725

1725

Model RDP Units

Model

Number
Average CFM /

Maximum CFM
Normal / Maximum

Sound Levels
Primary Motor

Maximum RPM
Secondary Motor

Maximum RPM
RDP-12
65.24 / 1370
60 db / 70 db
3000
1725
RDP-16
79.03 / 2450
60 db / 70 db
2000
1725
>RDP-20
73.98 / 4069
60 db / 70 db
1725
1725
RDP-24
61.77 / 4633
60 db / 70 db
1725
1725

Normal sound level tested in acoustic sound chamber with primary fan engaged and door sealed

Complete Information & Hardware are included with each Unit, to make installation a fast and easy process!
Please contact a Bebco Sales Associate to receive advanced copies of our installation, operation and maintenance manual.

All Units are furnished with the following
documentation and warning nameplate:

  • One (1) 24 Page Unit Installation, Operation & Maintenance Manual
  • One (1) Quality Control Inspection Report w/ Performance & Test Results
  • One (1) Product Registration Form (essential for extended warranty terms)
  • One (1) Electrical Wiring Diagram
  • One (1) VFD User’s Manual
  • One (1) Model CWN Personnel Door Caution Warning Nameplate

In addition, Model WDP Wall Mount Units are
shipped with the following Accessors:

  • One (1) Seal-Welded Interior Trim Bezel with Fasteners
  • Four (4) Exterior Mounting Flanges with Fasteners

Additional Manuals and Wiring Diagrams, along with additional Personnel Door Caution Nameplates and Equipment Door Warning Nameplates are available with each Unit attime of order placement, upon request.

Bebco supplies all essential documents and hardware to complete your installation and offers comprehensive support as required to assist you with installation and start-up!

Bebco Model WDP & RDP Whisper Drive™ Building Pressurization Unit Documents & Hardware

Bebco provides a comprehensive 24 page full color installation, operation and maintenance manual with every unit, along with a personnel door warning nameplate, an electrical wiring diagram and a VFD user’s manual. In addition, Model WDP Wall Mount Units are provided with ample gasket, fasteners, a seal-welded interior trim bezel and four (4) miter-cut exterior mounting flanges to mount the Model WDP Unit
through your building wall.