Bebco applies Adsil ® MicroGuard ® Siloxane Coatings as a dry film thickness of 6-8 microns, which provides exceptional resistance to fungal growth to meet ASTM-G21 and to resist high temperatures as tested to ASTM-D2485.
This coating achieves compliance to ASTM-B117, for 6,000 hours of exposure in a salt chamber. It also achieves significant abrasion resistance in accordance with AST-D4060 and forms an exceptionally bond to pre-coated OEM coils.
TECHNICAL BULLETIN
Adsil & MicroGuard are registered trademarks of the Adsil Corporation.

Bebco applies Heresite ® ES-600 Epoxy-Silane Coatings at a dry film thickness of 1.0-1.5 mils, to provide exceptional resistance to harsh solvents including acetone, in accordance with ASTM-D5402.
This coating also achieves compliance to ASTM B117 and ISO 12944-9 testing to pass 3,500 hours of salt spray and 4,200 hours of cyclic corrosion for off-shore facilities, with an ASTM-D3363 hardness rating of 2H-4H.
TECHNICAL BULLETIN
Heresite is a registered trademark of
Heresite Protective Coatings, LLC.

Bebco applies Modine ® ES2 Insitu ® Water Based Synthetic Flexible Polymer Coatings with embedded stainless steel pigments at a dry film thickness of 0.6 to 1.2 mils. This coating facilitates rapid heat dissipation and provides no less than 5,000 hours of salt spray resistance to ASTM-B117-11.
This coating is also extremely resistant to UV rays and it provides exceptional C5-I chemical resistance, in accordance with
ISO Test Method 2812-1.
TECHNICAL BULLETIN
Modine & Insitu are registered trademarks
of Modine Manufacturing Company.
IMPORTANT NOTES
Bebco Environmental Controls is authorized to utilize all coatings as herein listed in exact accordance
with factory training and quality assurance processes, to ensure the integrity of all coating applications.
Manufacturers are listed in alphabetical order, as not to unduly influence our Client's selection of a preferred coating.
|
Refrigerant System Coatings
Bebco enhances your refrigerant system performance by providing three premier
brands of protective coatings for the coils and refrigerant tubing of all condenser units.
These coatings protect units subjected to mild, moderate or extremely corrosive onshore, near shore or offshore environments.
Please review the information and technical bulletin links to the left to learn more about each coating's composition and ratings.
Bebco provides these options for mild to highly corrosive environments!
Click any image to learn more! |
|
Heresite Coatings
Optional for Units with EC Case StylesStandard For Units with CS & CX Case Styles
Prevents premature corrosion of vital refrigerant system
components!
•
•
• |
Applications:
Optional
Inclusion:
Standard
Inclusion: |
Mild to Extremely Corrosive
or Offshore Environments
Units with EC
Case Style
Units with CS & CX
Case Styles
|
Heresite ES 600 Coatings are applied on all Condenser Units with CS & CX Csae Styles, unless specifically
excluded at time of order. |
|
|
Adsil , Modine & Custom Coatings
Optional for all Units
Please contact a Bebco Sales Associate for more inrormation regarding these optional coatings
•
|
Applications:
|
Moderate to Extremely Corrosive
or Offshore Environments
|
Bebco offers Adsil, Modine and Custom
coatings under special circumstances only.
Please consult a Bebco Sales Associate now
for more information regarding these options. |
|
|
Bebco Model SAC & SHP
Split System Air Conditioner &
Heat Pump Condenser Units
that feature Coil Coatings
are provided with a detailed
preventive maintenance
instruction nameplate!
This ensures that
maintenace personell
are aware of this critical
feature, and perform proper
service to protect the coil coating!
|
Bebco Model SAC & SHP Split System Air Conditioner & Heat Pump Units
are provided with optional premier refrigerant system coating options that
you may select at time of order to meet your specific requirements! |
IMPORTANT NOTES
Bebco Environmental Controls is authorized to utilize all coatings as herein listed in exact accordance
with factory training and quality assurance processes, to ensure the integrity of all coating applications.
|
|